T E S T R E P O R T 1, ASTM E 90 09 Laboratory Measurement of Airborne Sound Transmission of. Building Partitions and Elements,TEST ACCREDITATION. Client Serious Energy Inc,Report Date January 13 2012. Test Date November 17 2011 For the scope of accreditation. Test Number OL 11 1110 under NVLAP code 200248 0,RESULT SUMMARY PREPARED BY. David M Berg,Orfield Laboratories Inc,CLIENT 2709 East 25th Street.
ADDRESS Minneapolis MN 55406,Serious Energy Inc Voice 612 721 2455. 1250 Elko Drive FAX 612 721 2457,Sunnyvale CA 94089 e mail dave orfieldlabs com. email info SeriousEnergy com,Prepared by Reviewed by. David M Berg Michael R Role,Laboratory Manager, Signatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only. T E S T R E P O R T,Project Sound Transmission Loss Testing 2.
Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110, Test Date November 17 2011 Method ASTM Standard E90. Specimen Wall Assembly Technician D Berg,Single Number Rating. Freq TL Def,Measured Result Limited Result,Transmission Loss dB. 20 2000 53,10 3150 54,Total Deficiencies 11,Estimate of lower limit. Frequency Band Hz, Assembly Elements listed in order from source room side to receiver room side.
0 625 5 8 QuietRock ES v 1 25 type S12 screws 12 O C. 3 5 8 20 gauge 0205 steel studs 16 O C,3 1 2 fiberglass insulation batts. 0 625 5 8 type X gypsum board vs 1 25 type S12 screws 12 O C. NVLAP Lab Code 200248 0,T E S T R E P O R T,Project Sound Transmission Loss Testing 3. Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110,SPECIMEN DESCRIPTION, The specimen under test was a wall assembly The elements in the assembly. are described briefly below the results table and chart on page 2 Detailed. information regarding the specimen may be found in Appendix C. Test results pertain to this specimen only,INSTALLATION AND DISPOSITION. The steel stud frame was originally constructed on November 17 2011 The. steel stud frame was retained from previous tests and was used for. subsequent tests in this series The entire assembly was constructed by. independent contractors Qualified representatives of Orfield Laboratories. observed the installation in progress and visually inspected the specimen prior. to testing,TEST METHODS,The methods followed these published standards.
ASTM E90 09 Standard Test Method for Laboratory Measurement of. Airborne Sound Transmission Loss of Building Partitions and Elements. ASTM E413 10 Classification for Rating Sound Insulation. The values presented in this report are from single direction. transmission loss measurements, Orfield Laboratories Inc has been accredited by the U S Department of. Commerce National Institute of Standards and Technology NIST under their. National Voluntary Laboratory Accreditation Program NVLAP for this test. procedure This report shall not be used to claim product endorsement by. NVLAP or any agency of the U S Government,CONFIDENTIALITY. The client has full control over this information and any release of information. will be only to the client The specific testing results are deemed to be. confidential exclusively for the client s use Reproduction of this report except. in full is prohibited,NVLAP Lab Code 200248 0,T E S T R E P O R T. Project Sound Transmission Loss Testing 4, Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110,APPENDIX A MEASUREMENT SETUP,Environment.
Temperature 68 F 20 0 C,Relative Humidity 50,Specimen Area. Specimen Area 64 5 ft 5 99 m,Chamber Volume Airborne Transmission. Source Room Volume 3284 ft 93 0 m,Receiving Room Volume 8281 ft 234 5 m. INSTRUMENTATION,Description Brand Model S N,Calibrator Br el Kj r Type 4230 1379712. Microphone Br el Kj r Type 4134 296819,Preamplifier Br el Kj r Type 2639 1202479.
Microphone Br el Kj r Type 4134 1675265,Preamplifier Br el Kj r Type 2639 1312147. Power Supply Br el Kj r Type WB1057 n a,Analyzer Norsonic Type 121 31185. NVLAP Lab Code 200248 0,T E S T R E P O R T,Project Sound Transmission Loss Testing 5. Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110,APPENDIX B CALCULATION RESULTS,Freq Specimen 95 Flanking STC. Band T L Conf Limit Defic,Hz dB dB dB dB,31 5 29 3 40.
40 17 7 47,50 16 7 43,63 15 7 43,80 12 4 3 04 41,100 14 9 3 11 46. 125 24 3 1 39 51 8,160 32 4 1 22 55 3,200 39 8 1 53 57. 250 43 2 1 70 60,315 48 5 0 98 60,400 50 6 0 99 61. 500 53 7 0 82 66,630 56 6 0 69 68,800 58 1 0 60 72. 1000 60 7 0 50 75,1250 61 4 0 56 72,1600 58 7 0 44 73.
2000 52 8 0 35 77,2500 51 7 0 63 81,3150 54 1 0 58 84. 4000 58 6 0 47 78,10000 65 7,Total deficiencies below STC contour dB 11. STC contour ASTM E413 48, Actual transmission loss of specimen may be higher than measured at this frequency. band Signal to noise in the receiving room less than 5 dB therefore the result is an. estimate of the lower limit, Note 95 confidence intervals from room qualification data Flanking Limit from. chamber flanking study Reference sample and repeatability data available upon request. Extended frequency results below 80Hz and above 5000Hz are for reference only. NVLAP Lab Code 200248 0,T E S T R E P O R T,Project Sound Transmission Loss Testing 6.
Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110,APPENDIX C SPECIMEN ASSEMBLY DESCRIPTION. The following table shows the elements in the wall assembly in order from the. source room to receiving room Independent contractors constructed and. installed the wall assembly in the laboratory test opening A qualified. representative of Orfield Laboratories observed the installation in process and. visually inspected the completed specimen and seals All materials were. weighed prior to installation Fastener weights are not included in the reported. Overall Mass 365 8 lb 165 9 kg,Overall Surface Density 5 67 PSF 27 69 kg m. Mass Surf Dens,Element lb kg PSF kg m, 0 625 5 8 QuietRock ES v 1 25 type S12 screws 12 O C 175 0 79 4 2 71 13 25. 3 5 8 20 gauge 0205 steel studs 16 O C 34 0 15 4 0 53 2 57. 3 1 2 fiberglass insulation batts 13 8 6 3 0 21 1 04. 0 625 5 8 type X gypsum board vs 1 25 type S12 screws 12 O C 143 0 64 9 2 22 10 82. The QuietRock ES EZ SNAP noise reducing drywall and QuietSeal Pro. acoustical sealant were supplied by the Client All other materials were. purchased through independent retail suppliers and were acquired by the. independent construction contractors The frame and insulation were. constructed for previous tests in this series for this client and portions of this. specimen assembly were used in subsequent tests in the series. A 3 5 8 20 gauge 0205 steel frame was constructed in the perimeter of the. laboratory test specimen opening The frame consisted of 20 gauge 0205. steel 3 5 8 x 1 1 4 track plate at the top and bottom and seven 3 5 8 x 1. 1 4 20 gauge 0205 steel studs installed 16 on center The track plates. and studs were fastened together with two type S pan head screws at each. intersection The perimeter of the frame was sealed to the specimen opening. with QuietSeal Pro acoustical sealant,INSULATION, Fiberglass insulation batts were installed in the stud cavities The insulation. batts were 16 wide 3 1 2 thick R13 and were friction fit into each of the six. stud cavities Figure 1 is a photograph of the insulated frame before the. installation of the sheeting layers,NVLAP Lab Code 200248 0.
T E S T R E P O R T,Project Sound Transmission Loss Testing 7. Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110, Figure 1 Insulated steel stud frame viewed from receiving room side. The single source room side sheeting layer consisted of two 5 8 thick 4 by 8. sheets of QuietRock ES EZ SNAP noise reducing drywall The QuietRock. ES sheets were fastened parallel to the steel stud frame with 1 1 4 long type. S12 drywall screws spaced at 12 on center The single layer was comprised. of two complete 4 by 8 sheets Figure 2 is a photograph of the source side. Figure 2 Source room side QuietRock ES installed and sealed in the. specimen opening,NVLAP Lab Code 200248 0,T E S T R E P O R T. Project Sound Transmission Loss Testing 8, Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110, The single receiving room side sheeting layer consisted of two 5 8 thick 4 by.
8 sheets of type X gypsum panels The type X gypsum sheets were fastened. parallel to the steel stud frame with 1 1 4 long type S12 drywall screws. spaced at 12 on center On the receiving room side the sheeting was. comprised of three sections to provide seams that were staggered from those. on the source side Figure 3 is a photograph of the receiving room side. Figure 3 Receiving room side sheeting installed and sealed in the specimen. Panels were shimmed at installation so equal gaps were at the top and bottom. Gaps were less than 1 4 in all cases Shims were removed after sheeting was. fastened and the vertical seams were sealed on the source and receiving room. sides with QuietSeal Pro acoustical sealant and 1 7 8 wide 5 mil aluminum foil. tape The perimeter of both sides of the sample were sealed with QuietSeal. Pro acoustical sealant 5 mil aluminum foil tape and 7 8 dense putty tape. NVLAP Lab Code 200248 0,T E S T R E P O R T,Project Sound Transmission Loss Testing 9. Client Serious Energy Inc of 9 Orfield Laboratories Inc. Test OL 11 1110,APPENDIX D SINGLE NUMBER CALCULATION TO ISO 717 1. Freq Ri Ref Unfav Li1 Li1 Ri Li2 Li2 Ri, Band R i TL Curve Deviat Spectrum Level Spectrum Level. Hz dB dB dB dB dB dB dB,100 14 9 30 15 1 29 0 43 9 20 0 34 9. 125 24 3 33 8 7 26 0 50 3 20 0 44 3,160 32 4 36 3 6 23 0 55 4 18 0 50 4.
200 39 8 39 21 0 60 8 18 0 57 8,250 43 2 42 19 0 62 2 15 0 58 2. 315 48 5 45 17 0 65 5 14 0 62 5,400 50 6 48 15 0 65 6 13 0 63 6. 500 53 7 49 13 0 66 7 12 0 65 7,630 56 6 50 12 0 68 6 11 0 67 6. 800 58 1 51 11 0 69 1 9 0 67 1,1000 60 7 52 10 0 70 7 8 0 68 7. 1250 61 4 53 9 0 70 4 9 0 70 4,1600 58 7 53 9 0 67 7 10 0 68 7.
2000 52 8 53 0 2 9 0 61 8 11 0 63 8,2500 51 7 53 1 3 9 0 60 7 13 0 64 7. 3150 54 1 53 9 0 63 1 15 0 69 1,Sum 28 9 R A 1 42 4 R A 2 34 2. RW 49 C 7 C tr 15,Rw C Ctr 49 7 15,Rw C Ctr C 50 3150 Ctr 50 3150 49 7 15 9 19. Rw C Ctr C 100 5000 Ctr 100 5000 49 7 15 6 15,Rw C Ctr C 50 5000 Ctr 50 5000 49 7 15 8 19. Note The calculations in ISO 717 1 are performed based on assumed. equivalency of the ASTM and the corresponding ISO test methods The test. herein is performed according to the ASTM standards Orfield Laboratories. does not hold accreditation for ISO 140 or ISO 717 under their NVLAP scope of. accreditation, The spectrum adaptation terms C and Ctr characterize performance against two.
specific sound sources A weighted pink noise and A weighted traffic noise. respectively The standard ISO 717 1 includes a discussion of Use of. Spectrum Adaptation Terms in Annex A informative, Each spectrum adaptation term may additionally be reported with extended. frequency bands included A calculation for the primary frequency range is. shown above but all available extended frequency calculations were. performed to compare against corresponding ratings of other specimens.


Related Books

ISO (INDIAN SCIENCE OLYMPIAD)

ISO INDIAN SCIENCE OLYMPIAD

ISO (INDIAN SCIENCE OLYMPIAD) SAMPLE PAPER 2018-19 Class : X Time allowed : 1 hours Maximum Marks :80 Please read the instructions in Question Booklet before answering the question paper. INSTRUCTIONS Before starting the paper, fill up the required details in the blank space provided in the answer sheet.

COMPLAINT DECLARATORY JUDGMENT, EQUITABLE RELIEF, ACTS OF ...

COMPLAINT DECLARATORY JUDGMENT EQUITABLE RELIEF ACTS OF

Plaintiff was initiated into the Beta Eta Chapter of Delta Sigma Theta Sorority, Inc. 7. During her undergraduate years Alabama State University, the Plaintiff majored in Theatre Arts, won the coveted title of Miss Alabama State University, served as the Step Team Captain of the Beta Eta chapter as well as its treasurer. 8. While a member of ...

2017 EDITION - Delta Sigma Theta

2017 EDITION Delta Sigma Theta

DELTA SIGMA THETA SORORITY, INCORPORATED PREAMBLE We, the duly constituted Grand Chapter of the Delta Sigma Theta Sorority, Inc., in order to form a closer union among college educated women for the fostering of high ideals in moral, social, and intellectual life, and the assisting of our

Texting Abbreviations, 2014

Texting Abbreviations 2014

Text-Message-Acronyms-of-2011.htm January, 2014 2014 is all about quick and mobile internet. Our desktop messaging has progressively shortened into millennial jargon, while our handheld text messaging is even more abbreviated to accommodate thumb typing. Yet we still need to pack in meaningful information, courtesy and etiquette into our messages.

Lesson #1. Introduction: Cardinal directions and compass

Lesson 1 Introduction Cardinal directions and compass

3 Hela Venture: Orienteering Lesson Plans Navigation activity Exploring & Navigating Purpose: Explore the outdoor area, while practicing using maps and the cardinal directions. Equipment Needed: Controls, Compass, printed map of the area with cardinal directions on the edges (a screenshot of a Google map works well). 1. Introduce participants to a compass. It is ideal if they can have one per

OMEGA Coaching Manual - Netball Australia

OMEGA Coaching Manual Netball Australia

The age of the netball players and their skill level is also an important consideration and coaches will need to take this into account when selecting the training drills to use. Each skill in the Manual is described with specific tips on execution of the skill. Where appropriate

Handbook of Industrial Drying, Fourth Edition

Handbook of Industrial Drying Fourth Edition

agriculture, building construction, materials, and chemicals are fundamental for LCA studies. There are initiatives in var-ious countries to collect such data or develop databases (often referred to as life cycle inventory [LCI]) for LCA, which are sometimes interlinked under the leadership of government or

Aerospace Threaded Fastener Strength in Combined Shear and ...

Aerospace Threaded Fastener Strength in Combined Shear and

t_thread ratio of applied tensile load to thread allowable tensile load = P/Pallow_thread V shear load applied to a bolt ... Aerospace Threaded Fastener Strength in ...

ISO 14971:2007 Risk Management Client Completion Form

ISO 14971 2007 Risk Management Client Completion Form

F 027b - Compliance Report ISO 14971:2007 - Revision 0.2 Purpose The purpose of this client completion form is to document the location of the required objective evidence of compliance with the risk management requirements of ISO 14971:2007 for compliance review. General Information

ACME/STUB ACME Thread Strength Calculation -Wihaga- Scope

ACME STUB ACME Thread Strength Calculation Wihaga Scope

ACME/STUB ACME Thread Strength Calculation -Wihaga- ... Thread Shear Area is ... assuming that both the pin and box have the same yield strength, etc. Shear (thread ...